Monitoring of the "Kosmos" store of "Vitpromtorg" LLC was carried out
In August 2024, employees of the department conducted a monitoring of the "Cosmos" store of "Vitpromtorg" LLC. During the monitoring, the following violations were identified:
failure to ensure the training of facility employees responsible for fire safety, who are assigned the duties of conducting fire safety briefings, according to the fire-technical minimum programs in accordance with the requirements of the Ministry of Emergency Situations;
fire safety briefings were not conducted with employees using the facility-wide fire safety instructions;
development of facility-wide fire safety instructions was not organized;
operability and serviceability of fire protection and fire extinguishing equipment, as well as constant readiness for their use, were not ensured (the seal on the OP-4 fire extinguisher located in the sales area is broken, the pressure gauge needle is in the red sector);
the facility lacks a fire safety information stand;
the facility is not equipped with primary fire extinguishing means in accordance with the norms established by the Ministry of Emergency Situations (it is necessary to add 4 OP-8 fire extinguishers in the sales area);
the possibility of opening locks (latches) on doors located on evacuation routes from the inside without a key was not ensured (external evacuation doors at the main entrance);
locations of fire extinguishers and manual fire alarms in the building are not marked with fire safety signs in accordance with GOST 12.4.026-2015 "Signal colors, safety signs and marking. Purpose and rules of use. General technical requirements and specifications. Test methods";
maintenance of the fire alarm system was not ensured;
a schedule for scheduled maintenance of automatic fire alarm and fire notification systems was not developed and approved;
recording of maintenance work on the system in the maintenance and current repair work log was not ensured;
control over the quality of system maintenance work was not ensured;
the height of thresholds in the doors of evacuation exits from the building is more than 0.06 m (main and emergency exits from the building);
a 10% reserve of fire detectors was not ensured at the facility, clause 8.3.11 of TKP 316-2011.
Following the monitoring results, recommendations for rectifying the violations have been sent to Vitpromtorg LLC.