Monitoring was carried out
In May 2025, employees of the Rossonsky District Department for Emergency Situations conducted a monitoring of the fire safety status of the Rossonsky unit of the Verkhnedvinsk branch of the Vitebsk Regional Consumer Society (Head – Stovpets R.V.).
The following violations were identified during the monitoring:
orders were not provided;
officials were not trained according to programs No. 1, 3, fire technical minimum (Rubashenko S.E., Reshetkina O.P., Pokatova E.A., Klachek S.N., Kovalchuk I.V., Kurzova M.V., Podvitelsky T.I., Zaykina L.V., Nabukhotnaya A.I., Vorobyeva M.B., Kabanova I.A., Koptelevа T.P., Danchenko V.K., Kovaleva E.L., Moiseeva V.I.), clause 4.1 of clause 4 of the "General fire safety requirements for the maintenance and operation of capital structures (buildings, structures), isolated premises and other facilities owned by business entities", approved by Decree of the President of the Republic of Belarus No. 7 of 23.11.2017 "On the Development of Entrepreneurship" (hereinafter referred to as OTРБ);
fire safety briefings were not conducted with employees using the general fire safety instructions for the facility, clause 4.1 of clause 4 of OTРБ, clause 6 of the Instruction on the procedure for training employees on fire safety issues and verifying their knowledge in this area, approved by the Ministry of Emergency Situations No. 82;
Rodny Kut Store, village Selyavshchina, Tsentralnaya St., 34
the operability and serviceability of fire protection and fire extinguishing means were not ensured (autonomous
The possibility of unlocking locks (latches) on doors located on evacuation routes (external evacuation doors) from the inside without a key is not ensured, clause 48 of the OTPB;
the facility is not equipped with primary fire extinguishing means in accordance with the norms determined by the Ministry of Emergency Situations (it is necessary to add 1 OP-8 and 1 OP-4 or 3 OP-4), clause 53 of the OTPB, clause 57 of the appendix to the Instruction on the norms for equipping facilities with primary fire extinguishing means, approved by the Minister of Emergency Situations No. 82;
Shop, Yankovichi village, Tsentralnaya St., 2
the operability and serviceability of fire protection and fire extinguishing means are not ensured (fire alarms require battery replacement), clauses 4.1, clause 4 of the OTPB;
the locations of fire extinguishers are not marked with fire safety signs in accordance with GOST 12.4.026-2015 "Signal colors, safety signs and signal marking. Purpose and rules of application. General technical requirements and characteristics. Test methods", clauses 4.1, clause 4 of the OTPB;
fire extinguishers in the building are placed on the floor, sub-clause 4.1 of clause 4 of the OTPB, clause 4.2.3 of TKP 295-2011 "Fire equipment. Fire extinguishers. Requirements for selection and operation";
The possibility of unlocking locks (latches) on doors located on evacuation routes (external evacuation doors (two doors) and the emergency exit door) from the inside without a key is not ensured, clause 48 of the OTPB;
the facility is not equipped with primary fire extinguishing means in accordance with the norms determined by the Ministry of Emergency Situations (it is necessary to add 1 OP-8 or 2 OP-4), clause 53 of the OTPB, clause 57 of the appendix to the Instruction on the norms for equipping facilities with primary fire extinguishing means, approved by the Minister of Emergency Situations No. 82;
Shop "Rodny Kut", Sokolishe agro-town, General Kulnev St., 30
the fire evacuation plan does not comply with the requirements of the Minister of Emergency Situations No. 82 (fire hydrants are mentioned, although they are absent in the building), clause 45 of the OTPB;
the locations of fire extinguishers are not marked with fire safety signs in accordance with GOST 12.4.026-2015 "Signal colors, safety signs and signal marking. Purpose and rules of application. General technical requirements and characteristics. Test methods", clauses 4.1, clause 4 of the OTPB;
fire extinguishers in the building are placed on the floor, sub-clause 4.1 of clause 4 of the OTPB, clause 4.2.3 of TKP 295-2011 "Fire equipment. Fire extinguishers. Requirements for selection and operation";
Locks (latches) on doors located on evacuation routes (external evacuation doors (two doors) and emergency exit door) cannot be freely opened from the inside without a key, para. 48 of the OTPB;
the facility is not equipped with primary fire extinguishing means in accordance with the norms established by the Ministry of Emergency Situations (it is necessary to add 1 OP-8 or 2 OP-4), para. 53 of the OTPB, para. 57 of the Annex to the Instruction on the norms for equipping facilities with primary fire extinguishing means, approved by the MES Order No. 82;
fire protection and fire extinguishing means are not operational and in good repair (fire automation systems are dismantled), para. 4.1, para. 4 of the OTPB;
the chimney of the heat-generating apparatus is made of materials not provided for by the TNPA (asbestos-cement pipe), para. 27 of the OTPB, para. 10 of the Instruction on requirements for the placement and operation of heat-generating apparatuses and heating devices of industrial (factory) production, approved by the MES Order No. 82;
the clearance between the stove and combustible building structures is less than 10 cm, para. 27 of the OTPB, para. 8 of the Instruction on requirements for the placement and operation of heat-retaining stoves, approved by the MES Order No. 82, para. 6.5.13, para. C.2, table C.1 of Annex C to SN 4.02.03-2019 "Heating, Ventilation and Air Conditioning";
Shop "Rodny Kut", Golovchitsy village, Tsentralnaya St., 37
locations of fire extinguishers are not marked with fire safety signs in accordance with GOST 12.4.026-2015 "Signal colors, safety signs and signal marking. Purpose and rules of application. General technical requirements and characteristics. Test methods", clauses 4.1 of clause 4 OTPB;
fire extinguishers in the building are placed on the floor, sub-clause 4.1 of clause 4 OTPB, clause 4.2.3 TKP 295-2011 "Fire fighting equipment. Fire extinguishers. Requirements for selection and operation";
it is not ensured that locks (latches) on doors located on evacuation routes (main entrance door) can be opened freely from the inside without a key, clause 48 OTPB;
the facility is not equipped with primary fire extinguishing means in accordance with the norms determined by the Ministry of Emergency Situations (it is necessary to add 1 OP-8 or 2 OP-4), clause 53 OTPB, clause 57 of the annex to the Instruction on the norms for equipping facilities with primary fire extinguishing means, approved by the Minister of Emergency Situations No. 82;
operability and serviceability of fire protection and fire extinguishing equipment are not ensured (fire automation systems are inoperable (signals "Fire", "Attention" are displayed on the FACP), cl. 4.1 cl. 4 OTPB;
fire alarm system maintenance is not provided according to the schedule approved by the head, cl. 6.1 TKP 316-2011 "Fire extinguishing systems, smoke protection systems, fire alarm systems, fire alarm and evacuation control systems maintenance and repair system. Organization and procedure for work execution" (hereinafter - TKP 316-2011);
a 10% reserve of fire detectors is not provided at the facility, cl. 8.3.11 TKP 316-2011;
Shop "Produkty", Rossony urban settlement, Oktyabrskaya str., 3
locations of fire extinguishers and manual fire call points are not marked with fire safety signs in accordance with GOST 12.4.026-2015 "Signal colors, safety signs and signal marking. Purpose and application rules. General technical requirements and specifications. Test methods", cl. 4.1 cl. 4 OTPB;
fire extinguishers in the building are placed on the floor, subclause 4.1 of clause 4 OTPB, cl. 4.2.3 TKP 295-2011 "Fire equipment. Fire extinguishers. Requirements for selection and operation";
the possibility of freely opening locks (latches) from the inside without a key on doors located on evacuation routes (main and emergency exit doors) is not ensured, cl. 48 OTPB;
the fire evacuation plan does not comply with the requirements of PMCHS No. 82 (manual fire call points are not shown, not all fire extinguishers are shown) and is not placed in a visible location, cl. 45 OTPB;
operability and serviceability of fire protection and fire extinguishing equipment are not ensured (fire automation systems are inoperable (the "Attention" signal is displayed on the FACP), cl. 4.1 cl. 4 OTPB (a proposal for suspension (prohibition) of the subject's activities (its workshops, production sections), equipment dated 21.06.2024 No. 7 is in effect);
fire alarm system maintenance is not provided according to the schedule approved by the head, cl. 6.1 TKP 316-2011;
a 10% reserve of fire detectors is not provided at the facility, cl. 8.3.11 TKP 316-2011;
Restaurant "Rosinka", Rossony urban settlement, Khomchenovsky str., 3
locations of fire extinguishers, manual fire alarms are not marked with fire safety signs in accordance with GOST 12.4.026-2015 "Signal colors, safety signs and signal marking. Purpose and rules of use. General technical requirements and characteristics. Test methods", clauses 4.1, clause 4 of OTPB;
fire extinguishers in the building are placed on the floor, sub-clause 4.1 of clause 4 of OTPB, clause 4.2.3 of TKP 295-2011 "Fire equipment. Fire extinguishers. Requirements for selection and operation";
the possibility of unlocking locks (latches) from the inside without a key on doors located on evacuation routes (exit doors to the hall on the first floor, exit to the 3rd type staircase, main exit from the building) is not ensured, clause 48 of OTPB;
the fire evacuation plan does not comply with the requirements of the Ministry of Emergency Situations Order No. 82 (fire hydrants are incorrectly marked), clause 45 of OTPB;
the operability and serviceability of fire protection and fire extinguishing means are not ensured (fire automation systems are inoperable (fire control panel is turned off)), clauses 4.1, clause 4 of OTPB (a proposal for suspension (prohibition) of the subject's activities (its workshops, production sections), equipment dated 21.06.2024 No. 6 is in effect);
maintenance of the fire alarm system according to the schedule approved by the head is not ensured, clause 6.1 of TKP 316-2011;
a 10% reserve of fire detectors is not provided at the facility, clause 8.3.11 of TKP 316-2011;
transmission of fire, malfunction, and unauthorized opening of the device casing notifications to a room with round-the-clock duty of trained personnel or to the Ministry of Emergency Situations fire rescue unit is not ensured, clause 9 of OTPB, clause 13.1 of SN 2.02.03-2019;
operability and serviceability of fire protection and fire extinguishing means, fire water supply are not ensured (hose is not connected to the fire hydrant on the 1st floor), clauses 4.1, clause 4 of OTPB;
an assessment of the readiness for use of fire hydrants has not been carried out, clause 57 of OTPB, clauses 10, 12 of the Instruction on the procedure for checking the condition of external and internal fire water supply, approved by the Ministry of Emergency Situations Order No. 82;
Fast food cafe "Edа i kofe", Rossony urban settlement, Khomchenovskogo str., 3
locations of manual fire alarm call points are not marked with fire safety signs in accordance with GOST 12.4.026-2015 "Signal colors, safety signs and signal marking. Purpose and rules of application. General technical requirements and characteristics. Test methods", subclauses 4.1 of clause 4 OTPB;
fire extinguishers in the building are placed on the floor, subclause 4.1 of clause 4 OTPB, clause 4.2.3 TKP 295-2011 "Fire equipment. Fire extinguishers. Requirements for selection and operation";
the possibility of opening locks (latches) from the inside without a key on doors located on evacuation routes (2 doors of the main exit) is not ensured, clause 48 OTPB;
the fire evacuation plan does not comply with the requirements of PMChS No. 82 (fire hydrants are incorrectly marked), clause 45 OTPB;
maintenance of the fire alarm system according to the schedule approved by the head is not ensured, clause 6.1 TKP 316-2011;
a 10% reserve of fire detectors is not provided at the facility, clause 8.3.11 TKP 316-2011;
transmission of notifications about fire, malfunction, and unauthorized opening of the device housing to a room with round-the-clock duty of trained personnel or to the fire and rescue unit of the Ministry of Emergency Situations is not ensured, clause 9 OTPB, clause 13.1 SN 2.02.03-2019;
an assessment of the readiness for use of fire hydrants has not been carried out, clause 57 OTPB, subclauses 10, 12 of the Instruction on the procedure for checking the condition of external and internal fire water supply, approved by PMChS No. 82;
Shopping center, Rossony district, Sovetskaya str., 16
the possibility of opening locks (latches) from the inside without a key on doors located on evacuation routes (emergency exit doors) is not ensured, clause 48 OTPB;
fire cabinets in the building are made of combustible material, clause 9 OTPB, clause 5.6 STB 1953-2009 "Fire cabinets. General technical requirements and test methods";
the operability and serviceability of fire protection and fire extinguishing means, and fire water supply are not ensured (hoses are not connected to six fire hydrants), subclauses 4.1 of clause 4 OTPB;
locations of manual fire alarm call points are not marked with fire safety signs in accordance with GOST 12.4.026-2015 "Signal colors, safety signs and signal marking. Purpose and rules of application. General technical requirements and characteristics. Test methods", subclauses 4.1 of clause 4 OTPB;
fire evacuation plans do not comply with the requirements of the Ministry of Emergency Situations Order No. 82 (the phrase "People's Actions" is written as "Personnel Actions", the layout does not comply, fire extinguishers are incorrectly depicted) and are not placed in visible locations, clause 45 of the Fire Safety Regulations;
flammable materials (product packaging, furniture) are placed under the march of the evacuation staircase, clause 50 of the Fire Safety Regulations;
the facility is not equipped with primary fire extinguishing means in accordance with the norms established by the Ministry of Emergency Situations (fire extinguishers are missing on the 2nd floor of the building), clause 53 of the Fire Safety Regulations, clause 57 of the appendix to the Instruction on the norms for equipping facilities with primary fire extinguishing means, approved by the Ministry of Emergency Situations Order No. 82;
materials with unconfirmed fire-technical characteristics are used for finishing evacuation routes (the ceiling and walls are finished with PVC panels), clause 9 of the Fire Safety Regulations, clause 8.1.2 of SN 2.02.05-2020;
the operability and serviceability of fire protection and fire extinguishing means are not ensured (fire automation systems are inoperable (the "Fire" signal is displayed on the fire alarm control panel, loop No. 3 is bypassed, "Malfunction" signal on several loops), subclauses 4.1 of clause 4 of the Fire Safety Regulations;
maintenance of the fire alarm system according to the schedule approved by the head is not ensured, clause 6.1 of TKP 316-2011;
a 10% reserve of fire detectors is not provided at the facility, clause 8.3.11 of TKP 316-2011;
Transport Department, Rossony district, Nevelskaya str., 26
the operability and serviceability of fire protection and fire extinguishing means are not ensured (fire extinguishers OP-4 (no nozzle, not recharged), OP-5 (not recharged), OP-5 (not recharged), OP-5 (no nozzle, not recharged), OP-4 (not recharged) are faulty in the workshop, OP-3 (not recharged) is faulty in the dispatch office, OP-3 (no nozzle, not recharged) is faulty in the rest room), subclause 4.1 of clause 4 of the Fire Safety Regulations (eliminated during monitoring);
the locations of fire extinguishers are not marked with fire safety signs in accordance with GOST 12.4.026-2015 "Signal colors, safety signs and signal marking. Purpose and rules of use. General technical requirements and characteristics. Test methods", subclauses 4.1 of clause 4 of the Fire Safety Regulations;
indicators of categories for premises classified by explosion and fire hazard are not posted in full on the exterior of doors (gates), clause 19 of the Specific Fire Safety Requirements for explosion and fire hazardous production facilities, approved by Resolution of the Council of Ministers of the Republic of Belarus of 20.11.2019 No. 779 "On approval of specific requirements" (hereinafter - the Requirements);
vehicles are not equipped with primary fire extinguishing means in full in accordance with the norms established by the Ministry of Emergency Situations (GAZ vehicle with state registration number AE-2 9549 has no fire extinguishers, GAZ vehicle with state registration number AV-2 9581 has 1 OP-2 fire extinguisher, MTZ-82 tractor with state registration number VK-2 6061 has no fire extinguishers), clause 53 of the General Technical Regulations, clauses 14, 21 of the Annex to the Instruction on the norms for equipping facilities with primary fire extinguishing means, approved by the Order of the Minister of Emergency Situations No. 82;
Distribution warehouses, Rossony urban settlement, Nevelskaya St., 14
the facility is not equipped with primary fire extinguishing means in accordance with the norms established by the Ministry of Emergency Situations (it is necessary to add 2 OP-4 or 1 OP-8 fire extinguishers), clause 53 of the General Technical Regulations, clause 57 of the Annex to the Instruction on the norms for equipping facilities with primary fire extinguishing means, approved by the Order of the Minister of Emergency Situations No. 82 (eliminated during monitoring);
the possibility of unlocking locks (latches) from the inside without a key on doors located on evacuation routes (ramp exit doors, main exit doors) is not ensured, clause 48 of the General Technical Regulations;
the locations of fire extinguishers and manual fire alarms in the boiler room are not marked with fire safety signs in accordance with GOST 12.4.026-2015 "Signal colors, safety signs and signal marking. Purpose and rules of application. General technical requirements and characteristics. Test methods", clauses 4.1 of clause 4 of the General Technical Regulations;
people evacuation plans in case of fire do not comply with the requirements of the Order of the Minister of Emergency Situations No. 82 (fire hoses are mentioned, although they are absent, the placement of fire extinguishers is incorrect, the "You are here" indicator does not correspond to the location of the evacuation plan), clause 45 of the General Technical Regulations;
the operability and serviceability of fire protection and fire extinguishing means are not ensured (fire automation systems are inoperable (battery failed), clauses 4.1 of clause 4 of the General Technical Regulations;
maintenance of the fire alarm system according to the schedule approved by the head is not ensured, clause 6.1 of TКП 316-2011;
10% reserve of fire detectors is not provided at the facility, clause 8.3.11 of TKP 316-2011;
Workshop of Rossony settlement, Lapenko St., 9
locations of fire extinguishers are not marked with fire safety signs in accordance with GOST 12.4.026-2015 "Signal colors, safety signs and signal marking. Purpose and rules of application. General technical requirements and characteristics. Test methods", clauses 4.1 of clause 4 of OTPB;
fire extinguishers in the building are placed on the floor, sub-clause 4.1 of clause 4 of OTPB, clause 4.2.3 of TKP 295-2011 "Fire equipment. Fire extinguishers. Requirements for selection and operation";
Shop "Rodny Kut", ag. Klyastitsy, Tsentralnaya St., 56
fire extinguishers in the building are placed on the floor, sub-clause 4.1 of clause 4 of OTPB, clause 4.2.3 of TKP 295-2011 "Fire equipment. Fire extinguishers. Requirements for selection and operation";
the possibility of opening locks (latches) on doors located on evacuation routes (main and emergency exit doors) from the inside without a key is not ensured, clause 48 of OTPB;
the fire evacuation plan does not comply with the requirements of the Ministry of Emergency Situations Order No. 82 (manual fire detectors are not shown, the placement of fire extinguishers does not comply), clause 45 of OTPB;
the facility is not equipped with primary fire extinguishing means in accordance with the norms determined by the Ministry of Emergency Situations (it is necessary to add 1 OP-8 or 2 OP-4), clause 53 of OTPB, clause 57 of the appendix to the Instructions on the norms of equipping facilities with primary fire extinguishing means, approved by the Ministry of Emergency Situations Order No. 82;
materials with unconfirmed fire-technical characteristics are used for finishing evacuation routes (ceiling and walls are finished with PVC panels), clause 9 of OTPB, clause 8.1.2 of SN 2.02.05-2020;
operability and serviceability of fire protection and fire extinguishing means are not ensured (fire alarm systems are inoperable (the fire alarm control panel displays a "Fire" signal)), clauses 4.1 of clause 4 of OTPB;
fire alarm system maintenance is not provided according to the schedule approved by the head, clause 6.1 of TKP 316-2011;
a 10% reserve of fire detectors is not provided at the facility, clause 8.3.11 of TKP 316-2011;
Shop "Rodny Kut", Yukhovichi village, Druzhby str., 72
operability and serviceability of fire protection and fire extinguishing means are not ensured (automatic fire detectors require replacement of power elements), clauses 4.1 of clause 4 of OTPB (eliminated during monitoring);
The fire evacuation plan does not comply with the requirements of the Ministry of Emergency Situations Order No. 82 (a fire alarm control panel is depicted, although it is not present), clause 45 of the General Rules for Fire Safety;
fire extinguishers in the building are placed on the floor, sub-clause 4.1 of clause 4 of the General Rules for Fire Safety, clause 4.2.3 of TKhP 295-2011 "Fire Fighting Equipment. Fire Extinguishers. Requirements for Selection and Operation";
the possibility of unlocking locks (latches) from the inside without a key on the doors located on the evacuation routes (main exit doors) is not ensured, clause 48 of the General Rules for Fire Safety;
the facility is not equipped with primary fire extinguishing means in accordance with the norms established by the Ministry of Emergency Situations (it is necessary to add 1 OP-8 or 2 OP-4), clause 53 of the General Rules for Fire Safety, clause 57 of the appendix to the Instruction on the norms for equipping facilities with primary fire extinguishing means, approved by the Ministry of Emergency Situations Order No. 82;
Shop "Rodny Kut", village Gorbachyovo, Shkolnaya St., 30
fire extinguishers in the building are placed on the floor, sub-clause 4.1 of clause 4 of the General Rules for Fire Safety, clause 4.2.3 of TKhP 295-2011 "Fire Fighting Equipment. Fire Extinguishers. Requirements for Selection and Operation";
the possibility of unlocking locks (latches) from the inside without a key on the doors located on the evacuation routes (main exit doors, emergency exit doors, doors leading to the warehouse) is not ensured, clause 48 of the General Rules for Fire Safety;
the facility is not equipped with primary fire extinguishing means in accordance with the norms established by the Ministry of Emergency Situations (it is necessary to add 1 OP-8 or 2 OP-4), clause 53 of the General Rules for Fire Safety, clause 57 of the appendix to the Instruction on the norms for equipping facilities with primary fire extinguishing means, approved by the Ministry of Emergency Situations Order No. 82;
the locations of fire extinguishers and manual fire alarm call points are not marked with fire safety signs in accordance with GOST 12.4.026-2015 "Signal Colors, Safety Signs and Signal Marking. Purpose and Rules of Application. General Technical Requirements and Specifications. Test Methods", sub-clauses 4.1 of clause 4 of the General Rules for Fire Safety;
materials with unconfirmed fire and technical characteristics are used for finishing evacuation routes (ceiling and wall finishes are made of PVC panels), clause 9 of the General Rules for Fire Safety, clause 8.1.2 of SN 2.02.05-2020;
the operability and serviceability of fire protection and fire extinguishing means are not ensured (fire automation systems are inoperable (the battery has failed)), sub-clauses 4.1 of clause 4 of the General Rules for Fire Safety (a proposal to suspend (prohibit) the activities of the subject (its workshops, production sections), equipment dated June 21, 2024 No. 5 is in effect);
failure to ensure the transmission of fire, malfunction, and unauthorized opening of the device housing notifications to a room with round-the-clock trained personnel or to the fire and rescue unit of the Ministry of Emergency Situations, clause 9 of OTPB, clause 13.1 of SN 2.02.03-2019;
failure to ensure the maintenance of the fire alarm system according to the schedule approved by the head, clause 6.1 of TKP 316-2011;
failure to ensure a 10% reserve of fire detectors at the facility, clause 8.3.11 of TKP 316-2011;
Shop "Rodny Kut", Golubovo village, Pochtovaya St., 6
failure to ensure the operability and serviceability of fire protection and fire extinguishing means (fire detectors require battery replacement), clauses 4.1 of clause 4 of OTPB;
the fire evacuation plan does not comply with the requirements of MES Order No. 82 (instead of the phrase "Order of actions of people", "Personnel actions" is written, not all fire extinguishers are depicted, fire hydrants are mentioned, although they are not present), clause 45 of OTPB;
fire extinguishers in the building are placed on the floor, sub-clause 4.1 of clause 4 of OTPB, clause 4.2.3 of TKP 295-2011 "Fire equipment. Fire extinguishers. Requirements for selection and operation";
failure to ensure the possibility of unlocking locks (latches) on doors located on evacuation routes (main and emergency exit doors) from the inside without a key, clause 48 of OTPB;
the facility is not equipped with primary fire extinguishing means in accordance with the norms determined by the Ministry of Emergency Situations (1 OP-8 or 2 OP-4 needs to be added), clause 53 of OTPB, clause 57 of the appendix to the Instruction on norms for equipping facilities with primary fire extinguishing means, approved by MES Order No. 82;
the locations of fire extinguishers are not marked with fire safety signs in accordance with GOST 12.4.026-2015 "Signal colors, safety signs and signal marking. Purpose and rules of use. General technical requirements and characteristics. Test methods", clauses 4.1 of clause 4 of OTPB;
Shop "Produkty", Zaborye village, Internatsionalnaya St., 24
failure to ensure the operability and serviceability of fire protection and fire extinguishing means (fire detectors require battery replacement), clauses 4.1 of clause 4 of OTPB (eliminated during monitoring);
the fire evacuation plan does not comply with the requirements of MES Order No. 82 (not all fire extinguishers are depicted), clause 45 of OTPB;
fire extinguishers in the building are placed on the floor, sub-clause 4.1 of clause 4 of OTPB, clause 4.2.3 of TKP 295-2011 "Fire equipment. Fire extinguishers. Requirements for selection and operation";
The locks (latches) on the doors located on the evacuation routes (main exit doors) cannot be freely opened from the inside without a key, clause 48 of the OTPB;
The facility is not equipped with primary fire extinguishing means in accordance with the norms established by the Ministry of Emergency Situations (1 OP-4 needs to be added), clause 53 of the OTPB, clause 57 of the Annex to the Instruction on the Norms for Equipping Facilities with Primary Fire Extinguishing Means, approved by the MES Order No. 82;
The locations of fire extinguishers are not marked with fire safety signs in accordance with GOST 12.4.026-2015 "Signal Colors, Safety Signs and Signal Marking. Purpose and Application Rules. General Technical Requirements and Specifications. Test Methods", subclauses 4.1 of clause 4 of the OTPB;
Materials with unconfirmed fire-technical characteristics are used for finishing evacuation routes (ceiling and wall finishes are made of PVC panels, floor finish is made of linoleum), clause 9 of the OTPB, clause 8.1.2 of SN 2.02.05-2020;
Shop "Rodny Kut", agro-town Krasnopolye, Selskaya St., 10
The operability and serviceability of fire protection and fire extinguishing means are not ensured (API require battery replacement), subclauses 4.1 of clause 4 of the OTPB (rectified during monitoring);
The operability and serviceability of fire protection and fire extinguishing means are not ensured (2 API have been removed), subclauses 4.1 of clause 4 of the OTPB;
The fire evacuation plan does not comply with the requirements of MES Order No. 82 (not all fire extinguishers are depicted, a fire alarm control panel is depicted, although it is absent), clause 45 of the OTPB;
Fire extinguishers in the building are placed on the floor, subclause 4.1 of clause 4 of the OTPB, clause 4.2.3 of TKP 295-2011 "Fire Fighting Equipment. Fire Extinguishers. Requirements for Selection and Operation";
The locks (latches) on the doors located on the evacuation routes (main and emergency exit doors) cannot be freely opened from the inside without a key, clause 48 of the OTPB;
The facility is not equipped with primary fire extinguishing means in accordance with the norms established by the Ministry of Emergency Situations (1 OP-8 or 2 OP-4 needs to be added), clause 53 of the OTPB, clause 57 of the Annex to the Instruction on the Norms for Equipping Facilities with Primary Fire Extinguishing Means, approved by the MES Order No. 82;
locations of fire extinguishers are not marked with fire safety signs in accordance with GOST 12.4.026-2015 "Signal colors, safety signs and signal marking. Purpose and rules of application. General technical requirements and characteristics. Test methods", subclauses 4.1, clause 4 of OTPB;
materials with unconfirmed fire-technical characteristics are used for finishing evacuation routes (ceiling and wall finishing is made of PVC panels), clause 9 of OTPB, subclause 8.1.2 of SN 2.02.05-2020;
operability and serviceability of fire protection and fire extinguishing means are not ensured (fire extinguisher OP-4 in the boiler room is not recharged), subclauses 4.1, clause 4 of OTPB;
Shop, Albrechtovo village, Zhasminnaya street, 8
operability and serviceability of fire protection and fire extinguishing means are not ensured (API require replacement of power elements), subclauses 4.1, clause 4 of OTPB;
the fire evacuation plan does not comply with the requirements of PMCHS No. 82 (not all fire extinguishers are depicted, a fire alarm control panel is depicted, although it is absent), clause 45 of OTPB;
fire extinguishers in the building are placed on the floor, subclause 4.1, clause 4 of OTPB, subclause 4.2.3 of TKP 295-2011 "Fire equipment. Fire extinguishers. Requirements for selection and operation";
it is not ensured that locks (latches) on doors located on evacuation routes (main exit doors) can be opened freely from the inside without a key, clause 48 of OTPB;
the facility is not equipped with primary fire extinguishing means in accordance with the norms defined by the Ministry of Emergency Situations (it is necessary to add 1 OP-8 and 1 OP-4 or 3 OP-4), clause 53 of OTPB, clause 57 of the appendix to the Instruction on the norms for equipping facilities with primary fire extinguishing means, approved by PMCHS No. 82;
the locations of fire extinguishers are not marked with fire safety signs in accordance with GOST 12.4.026-2015 "Signal colors, safety signs and signal marking. Purpose and rules of application. General technical requirements and characteristics. Test methods", clauses 4.1 of clause 4 of OTPB.
Capital violations were also identified (recommended for implementation):
Shop "Rodny Kut", village Golovchitsy, Tsentralnaya St., 37
the detectors are installed at a height of less than 2.2 m from the floor level to their lower part without protection against mechanical damage, clauses 12.12.9 of SN 2.02.03-2019;
the distance between duplicate fire detectors is less than 1 m, clause 12.3.20 of SN 2.02.03-2019;
Shop "Produkty", urban-type settlement Rossony, Oktyabrskaya St., 3
the height of the threshold in the door of the evacuation exit to the outside is more than 0.06 m, clause 7.3.12 of SN 2.02.05-2020;
Restaurant "Rosinka", urban-type settlement Rossony, Khomchenovskogo St., 3
the detectors are installed at a height of less than 2.2 m from the floor level to their lower part without protection against mechanical damage, clauses 12.12.9 of SN 2.02.03-2019;
Fast food cafe "Eda i kofe", urban-type settlement Rossony, Khomchenovskogo St., 3
the detectors are installed at a height of less than 2.2 m from the floor level to their lower part without protection against mechanical damage, clauses 12.12.9 of SN 2.02.03-2019;
the "Exit" light sign is installed at a distance of more than 0.5 m above the doorway of the evacuation exit, clause 12.12.13 of SN 2.02.03-2019;
the height of the evacuation exit to the outside of the building is less than 1.95 m, clause 7.2.8 of SN 2.02.05-2020;
Shopping center, urban-type settlement Rossony, Sovetskaya St., 16
the detectors are installed at a height of less than 2.2 m from the floor level to their lower part without protection against mechanical damage, clauses 12.12.9 of SN 2.02.03-2019;
Distribution warehouses, urban-type settlement Rossony, Nevelskaya St., 14
the "Exit" light sign is installed at a distance of more than 0.5 m above the doorway of the evacuation exit, clause 12.12.13 of SN 2.02.03-2019;
the distance between duplicate fire detectors is less than 1 m, clause 12.3.20 of SN 2.02.03-2019;
Workshop, urban-type settlement Rossony, Lapenko St., 9
the building is not equipped with a fire alarm system, clause 14 of table F.1 of appendix F to SN 2.02.03-2019;
the building is not equipped with a system for notifying and managing the evacuation of people during a fire, clause 18.1.2 of table C.1 of appendix C to SN 2.02.03-2019;
the building is not equipped with a system for transmitting fire notifications, clause 3 of table X.1 of appendix X to SN 2.02.03-2019;
Shop "Rodny kut", village Yukhovichy, Druzhby St., 72
the height of the threshold in the door of the evacuation exit to the outside is more than 0.06 m, clause 7.3.12 of SN 2.02.05-2020;
Also, during the monitoring, violations were identified in the operation of electrical networks and equipment:
junction boxes are not closed (shop, village Yankovichi, Tsentralnaya St., 2; transport department, urban-type settlement Rossony, Nevelskaya St., 26; distribution warehouses, urban-type settlement Rossony, Nevelskaya St., 14; shop "Rodny kut", village Golubovo, Pochtovaya St., 6);
Lamps are missing shades (Rodny Kut store, Sokolishe village, 30 General Kulnev St.; Produkty store, Rossony town, 3 Oktyabrskaya St.; Rosinka restaurant, Rossony town, 3 Khomchenovsky St.; Shopping center, Rossony town, 16 Sovetskaya St.; Transport department, Rossony town, 26 Nevelskaya St.; Workshop, Rossony town, 9 Lapenko St.; Rodny Kut store, Yukhovichi village, 72 Druzhby St.; Rodny Kut store, Krasnopolye village, 10 Selskaya St.; Store, Albrekhtovo village, 8 Zhasminnaya St.).
The Ministry of Emergency Situations reminds that in accordance with Article 20 of the Law of the Republic of Belarus "On Fire Safety", heads of organizations must ensure fire safety and fire protection regulations in their respective organizations.